The 614P is capable of detecting the visible smoke produced by materials which smoulder or burn slowly, i.e. soft furnishings, plastic foam etc. or ‘smoke’ produced by overheated but unburnt PVC.

Description

The 614P is capable of detecting the visible smoke produced by materials which smoulder or burn slowly, i.e. soft furnishings, plastic foam etc. or ‘smoke’ produced by overheated but unburnt PVC. These detectors are particularly suitable for general applications and areas where cable overheating may occur; electrical services areas. The novel design of the asymmetrical sampling chamber and signal processing techniques stop unwanted alarms caused by very small insects. Smoke entering the sampling chamber scatters the infrared light pulses onto a photodiode. These pulses are converted to an electrical signal that is compared against a preset alarm level.

Specifications
– Operating Voltage 10 to 33Vdc
– Quiescent Current 60µA
– Alarm Current (max.)* 0.7 to 67mA (55°C)
0.7 to 60mA (70°C)
– Alarm State Voltage 2.5 to 7.4V
– Ext. Powered Load (max.) 50mA. 28Vdc
– Sensitivity (AS7240.7-2004) 4%Obs/m
– Remote Indicator E500 Mk2 Series
– Relative Humidity 10% to 95% (n/cond)
– Ambient Temperature -20°C to +70°C
– Dimensions (incl. base) 127 dia x 54H (mm)
– Weight 188g with base
– ActivFire Listed afp-1715
– FPANZ Listed VF/344