Description
The RIM800 Relay Interface Module provides one volt-free changeover contact which is not supervised. The relay is controlled by a command sent from the CIE via the addressable loop and may be used to signal a state to other systems (security systems, for example) or to energise loads such as Door Holders. The relay operation is determined by the CIE programming. The RIM800 has a red LED which may be configured to indicate relay activation and CIE polling. Note that the RIM800 cannot be used to switch mains voltage directly.
Specifications
– Operating Voltage 20 to 40Vdc*
– Quiescent Current 285µA (max.)
– Alarm Current 2.8mA (max, LED on)
– Relay Contact 2A @ 30Vdc (max.)
– Ambient Temp -25 to +70°C
– Relative Humidity 10% to 95% (n/cond)
– Dimensions (HWD) 61 x 84 x 25mm
– ActivFire Listed afp-1446
– FPANZ Listed VF/642
* MX addressable loop voltage