Description
The 4090-9118 Relay IAM with T-Sense allows a 4100ES IDNet communication channel to monitor two input contact closures with one point and control an output relay with the other point, yet occupy a single loop address. Power is supplied from the IDNet communications channel, eliminating the need for separate power wiring. The input circuit and relay operation are controlled independently and may be disabled separately. Applications include water flow and tamper switch monitoring and control and damper position monitoring and control
Specifications
– Comms Power 24 to 40Vdc w/data *
– Relay Contact Ratings SPDT
0.5A @120VAC**
0.25A@120VAC***
2A@30Vdc**
1A@30Vdc***
– Input N/O, dry contacts
– Current Limited Operation 1k8/4k7 0.5W
– Dimensions (HWD) 105 x 105 x 35 mm
– Ambient Temperature 0 to +49°C
– Relative Humidity 10% to 90% (n/c)
* IDNet communications with data
** Resistive Load
*** Inductive Load
Note: Loop powered 2 wire device