<?xml version="1.0" encoding="UTF-8"?><rss version="2.0"
	xmlns:content="http://purl.org/rss/1.0/modules/content/"
	xmlns:wfw="http://wellformedweb.org/CommentAPI/"
	xmlns:dc="http://purl.org/dc/elements/1.1/"
	xmlns:atom="http://www.w3.org/2005/Atom"
	xmlns:sy="http://purl.org/rss/1.0/modules/syndication/"
	xmlns:slash="http://purl.org/rss/1.0/modules/slash/"
	>

<channel>
	<title>Laserplus &#8211; Fire &amp; Safety WA</title>
	<atom:link href="http://fireandsafetywa.com.au/product-tag/laserplus/feed/" rel="self" type="application/rss+xml" />
	<link>http://fireandsafetywa.com.au</link>
	<description></description>
	<lastBuildDate>Mon, 05 Nov 2018 13:32:59 +0000</lastBuildDate>
	<language>en-AU</language>
	<sy:updatePeriod>
	hourly	</sy:updatePeriod>
	<sy:updateFrequency>
	1	</sy:updateFrequency>
	<generator>https://wordpress.org/?v=5.2.16</generator>

<image>
	<url>http://fireandsafetywa.com.au/wp-content/uploads/2018/04/cropped-favicon-32x32.png</url>
	<title>Laserplus &#8211; Fire &amp; Safety WA</title>
	<link>http://fireandsafetywa.com.au</link>
	<width>32</width>
	<height>32</height>
</image> 
	<item>
		<title>19&#8243; Rack c/w 4 Blanks</title>
		<link>http://fireandsafetywa.com.au/product/19-rack-c-w-4-blanks/</link>
				<pubDate>Sun, 07 Oct 2018 15:26:38 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/19-rack-c-w-4-blanks/</guid>
				<description><![CDATA[To compliment the VESDA range of detectors, displays and programmers in a 19 inch subrack enclosure is available.]]></description>
								<content:encoded><![CDATA[<p>To compliment the VESDA range of detectors, displays and programmers in a 19 inch subrack enclosure is available. The 19 inch rack enclosure is designed to house up to 12 display and/or programmer modules, VESDAnet sockets, or relay only modules<br />
in a wide variety of configurations to suit the particular requirements of a site where centralised control and monitoring of the VESDA system is required. VESDA Aspirating Smoke Detectors (ASD) are available in a wide range of configurations to suit the particular requirements of each site. The system is modular with Display and Programmer Modules located in the most convenient location. The backbone to this modularity is VESDAnet, a fault tolerant RS485 communications loop which links all elements of the VESDA system together.</p>
<p>Mounting Options<br />
Display and Programmer modules can be mounted in a Detector Enclosure, in a Remote Box or in a 19 inch subrack. A Hand-held programmer module is also available for temporary and convenient connection to the VESDA system. Details of these standard mounting options are given in the Detector, Display and Programmer Data sheets.</p>
<p>Relay Signalling<br />
Each Display Module can be configured to drive relays which can be used for reliable (fault tolerant) signalling of Fire and Fault conditions to external systems. Standard Display Modules can drive 7 relays while VESDA VLS Display Modules can be configured to drive 7 or 12 relays. Relay functionality is fully configurable according to site requirements.</p>
<p>19 inch Rack Enclosure<br />
19 inch subracks can be installed in glass fronted enclosures and are mounted on a swing frame for convenient connection of all the cables. Cable entry for 24 VDC power, VESDAnet connection and interfacing to the relays is provided by multiple knock-outs on all four sides of the box. 19 inch subracks and blank panels must be ordered separately. Each enclosure will accommodate up to 3 subracks. If utilising only 1 or 2 racks the VESDA Power Supply (VPS-100-US-xxx) can also be mounted in the enclosure.</p>
<p>Features<br />
&#8211; Dual hinged glass door provides easy access to VESDA modules and termination boards<br />
&#8211; Second door provides access to the termination boards<br />
&#8211; Designed for easy mounting<br />
&#8211; Multiple knock-outs for easy cable entry<br />
&#8211; Holds up to 3 subracks<br />
&#8211; Full size, lockable window and door</p>
<p>Technical Specifications<br />
Construction:<br />
&#8211; NEMA 1 Rating<br />
&#8211; 16 gauge cold roll steel<br />
&#8211; Fully welded and ground<br />
&#8211; Double knockouts<br />
&#8211; Continuous hinges with stainless steel pins<br />
&#8211; Full size window kit – lockable<br />
&#8211; Door – lockable (keyed alike with window)<br />
Mounting: Key hole mounting<br />
Finish: 2-part polyurethane – bake on textured finish<br />
Color: Light grey<br />
Locks: Keyed alike Chicago locks<br />
Blanking Plates:<br />
&#8211; 14 gauge cold roll steel<br />
&#8211; Light grey matching color<br />
&#8211; Single plate – 19 x 51/4 &#8221;<br />
&#8211; Double plate – 19 x 101/2&#8243;<br />
&#8211; Enclosure requires 4 10/32&#8243; screws for mounting 19 inch rack and/or blanking plates</p>
]]></content:encoded>
										</item>
		<item>
		<title>Remote Box with LaserCompact Display, 7 Relays</title>
		<link>http://fireandsafetywa.com.au/product/remote-box-with-lasercompact-display-7-relays/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/remote-box-with-lasercompact-display-7-relays/</guid>
				<description><![CDATA[VESDA Remote Display modules provide real-time indication of the status of a VESDA detector.]]></description>
								<content:encoded><![CDATA[<p>VESDA Remote Display modules provide real-time indication of the status of a VESDA detector. They have a 20-segment vertical bar graph display, a 2 digit numeric display, an audible sounder, clear alarm and fault indicators. They also have 4 push button keys to control the detector and the mode of the display.  The Display Module can be mounted into a detector unit, a remote mounting box or a 19in sub rack. Several displays can be configured to display information from a single detector in multiple locations.  There are various versions of the display module depending on the type of detector and the relay configuration required. The VESDA VLS display has a fourth mode for the Numerical Display which shows the First Alarm Sector (FAS), this being the number of the sector (pipe) that has detected smoke.  For the VESDA VLC the Fire 2 LED is omitted.</p>
<p>Smoke Indication<br />
Smoke levels are continuously shown on a bar graph display where each illuminated segment indicates the current level of detected smoke.  The top segment of the bar graph indicates the Fire 1 smoke threshold level and each segment below that level represents 1/20 of the Fire 1 smoke threshold level.  To the left of the bar graph are the Fire 1, Action and Alert smoke threshold indicators.  At a glance these provide a visual representation of the programmable alarm thresholds showing how close the smoke level is to<br />
triggering the next level of alarm.</p>
<p>Status Lights<br />
High intensity flashing LEDs provide a clear indication of the fire condition and are accompanied by an audible warning appropriate to the alarm condition.  Similarly, any fault condition is indicated by a series of LEDs and an audible tone providing a comprehensive range of status information.  The audible warning is easily silenced by pressing the Silence button at which point any flashing LEDs are illuminated until the cause of the event is identified, rectified and the system reset.</p>
<p>Numeric Display<br />
A 2 digit numerical readout has a number of modes that are indicated by up to four LEDs:<br />
&#8211; The current smoke level in % obscuration/m (% obscuration/ft)<br />
&#8211; Fire 1 threshold in % obscuration/m (% obscuration/ft). This is the sensitivity of the detector.<br />
&#8211; The VESDA zone number<br />
&#8211; First Alarm Sector on the VLS display &#8211; the numeric readout shows the sector (pipe) number that has detected smoke.</p>
<p>Push Button Keys<br />
Four large tactile push button keys enable users to reset, isolate or silence the detector and control the mode of the display module. The buttons can be disabled to prevent operation of it&#8217;s functions.  A lamp test routine is initiated by pressing the Mode key for two seconds.  A Manual Scan can be initiated on the VLS by holding the Silence button for 2 seconds.  </p>
<p>Features:<br />
&#8211; Provides Immediate Status Reporting for a Single VESDA Zone<br />
&#8211; Allows Zone Control of Assigned VESDA Detector<br />
&#8211; High Intensity Alarm LEDs<br />
&#8211; Remote Relay Option<br />
&#8211; 20-Segment Vertical Bar Graph Display<br />
&#8211; Alarm Threshold Indicators<br />
&#8211; Built-In Sounder for Audible Warning<br />
&#8211; Comprehensive Fault Reporting<br />
&#8211; Multi-mode Numeric Display (defaults to smoke obscuration)<br />
&#8211; Recessed Mounting Option</p>
<p>Specifications<br />
Operating Voltage (When used in detector unit, remote unit, or 19&#8243; rack): 18 to 30Vdc<br />
Operating Temp: 0 to 39° C<br />
Relative Humidity: 10 to 95% (non-cond.)</p>
<p>Module Only<br />
Dimensions (HWD): 130x105x30mm<br />
Operating Current: 60mA<br />
Alarm Current: 80mA @24Vdc</p>
<p>Mounted in Remote Box &#8211;<br />
Dimensions (WHD): 140 mm x 150 mm x 85 mm (5.5 in x 5.9 in x 3.4 in)<br />
Operating Current: 90mA<br />
Alarm Current: 110mA @24Vdc</p>
<p>The CRT-J00 is a VESDA VLC Display with a remote termination card. 7 Relays.</p>
]]></content:encoded>
										</item>
		<item>
		<title>Remote Box with VESDA VLI Display, 7 Relays</title>
		<link>http://fireandsafetywa.com.au/product/remote-box-with-vesda-vli-display-7-relays/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/remote-box-with-vesda-vli-display-7-relays/</guid>
				<description><![CDATA[VESDA Remote Display modules provide real-time indication of the status of a VESDA detector.]]></description>
								<content:encoded><![CDATA[<p>VESDA Remote Display modules provide real-time indication of the status of a VESDA detector. They have a 20-segment vertical bar graph display, a 2 digit numeric display, an audible sounder, clear alarm and fault indicators. They also have 4 push button keys to control the detector and the mode of the display.  The Display Module can be mounted into a detector unit, a remote mounting box or a 19in sub rack. Several displays can be configured to display information from a single detector in multiple locations.  There are various versions of the display module depending on the type of detector and the relay configuration required. The VESDA VLS display has a fourth mode for the Numerical Display which shows the First Alarm Sector (FAS), this being the number of the sector (pipe) that has detected smoke.  For the VESDA VLC the Fire 2 LED is omitted.</p>
<p>Smoke Indication<br />
Smoke levels are continuously shown on a bar graph display where each illuminated segment indicates the current level of detected smoke.  The top segment of the bar graph indicates the Fire 1 smoke threshold level and each segment below that level represents 1/20 of the Fire 1 smoke threshold level.  To the left of the bar graph are the Fire 1, Action and Alert smoke threshold indicators.  At a glance these provide a visual representation of the programmable alarm thresholds showing how close the smoke level is to<br />
triggering the next level of alarm.</p>
<p>Status Lights<br />
High intensity flashing LEDs provide a clear indication of the fire condition and are accompanied by an audible warning appropriate to the alarm condition.  Similarly, any fault condition is indicated by a series of LEDs and an audible tone providing a comprehensive range of status information.  The audible warning is easily silenced by pressing the Silence button at which point any flashing LEDs are illuminated until the cause of the event is identified, rectified and the system reset.</p>
<p>Numeric Display<br />
A 2 digit numerical readout has a number of modes that are indicated by up to four LEDs:<br />
&#8211; The current smoke level in % obscuration/m (% obscuration/ft)<br />
&#8211; Fire 1 threshold in % obscuration/m (% obscuration/ft). This is the sensitivity of the detector.<br />
&#8211; The VESDA zone number<br />
&#8211; First Alarm Sector on the VLS display &#8211; the numeric readout shows the sector (pipe) number that has detected smoke.</p>
<p>Push Button Keys<br />
Four large tactile push button keys enable users to reset, isolate or silence the detector and control the mode of the display module. The buttons can be disabled to prevent operation of it&#8217;s functions.  A lamp test routine is initiated by pressing the Mode key for two seconds.  A Manual Scan can be initiated on the VLS by holding the Silence button for 2 seconds.  </p>
<p>Features:<br />
&#8211; Provides Immediate Status Reporting for a Single VESDA Zone<br />
&#8211; Allows Zone Control of Assigned VESDA Detector<br />
&#8211; High Intensity Alarm LEDs<br />
&#8211; Remote Relay Option<br />
&#8211; 20-Segment Vertical Bar Graph Display<br />
&#8211; Alarm Threshold Indicators<br />
&#8211; Built-In Sounder for Audible Warning<br />
&#8211; Comprehensive Fault Reporting<br />
&#8211; Multi-mode Numeric Display (defaults to smoke obscuration)<br />
&#8211; Recessed Mounting Option</p>
<p>Specifications<br />
Operating Voltage (When used in detector unit, remote unit, or 19&#8243; rack): 18 to 30Vdc<br />
Operating Temp: 0 to 39° C<br />
Relative Humidity: 10 to 95% (non-cond.)</p>
<p>Module Only<br />
Dimensions (HWD): 130x105x30mm<br />
Operating Current: 60mA<br />
Alarm Current: 80mA @24Vdc</p>
<p>Mounted in Remote Box &#8211;<br />
Dimensions (WHD): 140 mm x 150 mm x 85 mm (5.5 in x 5.9 in x 3.4 in)<br />
Operating Current: 90mA<br />
Alarm Current: 110mA @24Vdc</p>
<p>The VRT-Q00 is a VESDA LaserINDUSTRIAL display with a remote termination card. 7 Relays.</p>
]]></content:encoded>
										</item>
		<item>
		<title>Remote Box with VESDA VLI Display No Relays</title>
		<link>http://fireandsafetywa.com.au/product/remote-box-with-vesda-vli-display-no-relays/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/remote-box-with-vesda-vli-display-no-relays/</guid>
				<description><![CDATA[VESDA Remote Display modules provide real-time indication of the status of a VESDA detector.]]></description>
								<content:encoded><![CDATA[<p>VESDA Remote Display modules provide real-time indication of the status of a VESDA detector. They have a 20-segment vertical bar graph display, a 2 digit numeric display, an audible sounder, clear alarm and fault indicators. They also have 4 push button keys to control the detector and the mode of the display.  The Display Module can be mounted into a detector unit, a remote mounting box or a 19in sub rack. Several displays can be configured to display information from a single detector in multiple locations.  There are various versions of the display module depending on the type of detector and the relay configuration required. The VESDA VLS display has a fourth mode for the Numerical Display which shows the First Alarm Sector (FAS), this being the number of the sector (pipe) that has detected smoke.  For the VESDA VLC the Fire 2 LED is omitted.</p>
<p>Smoke Indication<br />
Smoke levels are continuously shown on a bar graph display where each illuminated segment indicates the current level of detected smoke.  The top segment of the bar graph indicates the Fire 1 smoke threshold level and each segment below that level represents 1/20 of the Fire 1 smoke threshold level.  To the left of the bar graph are the Fire 1, Action and Alert smoke threshold indicators.  At a glance these provide a visual representation of the programmable alarm thresholds showing how close the smoke level is to<br />
triggering the next level of alarm.</p>
<p>Status Lights<br />
High intensity flashing LEDs provide a clear indication of the fire condition and are accompanied by an audible warning appropriate to the alarm condition.  Similarly, any fault condition is indicated by a series of LEDs and an audible tone providing a comprehensive range of status information.  The audible warning is easily silenced by pressing the Silence button at which point any flashing LEDs are illuminated until the cause of the event is identified, rectified and the system reset.</p>
<p>Numeric Display<br />
A 2 digit numerical readout has a number of modes that are indicated by up to four LEDs:<br />
&#8211; The current smoke level in % obscuration/m (% obscuration/ft)<br />
&#8211; Fire 1 threshold in % obscuration/m (% obscuration/ft). This is the sensitivity of the detector.<br />
&#8211; The VESDA zone number<br />
&#8211; First Alarm Sector on the VLS display &#8211; the numeric readout shows the sector (pipe) number that has detected smoke.</p>
<p>Push Button Keys<br />
Four large tactile push button keys enable users to reset, isolate or silence the detector and control the mode of the display module. The buttons can be disabled to prevent operation of it&#8217;s functions.  A lamp test routine is initiated by pressing the Mode key for two seconds.  A Manual Scan can be initiated on the VLS by holding the Silence button for 2 seconds.  </p>
<p>Features:<br />
&#8211; Provides Immediate Status Reporting for a Single VESDA Zone<br />
&#8211; Allows Zone Control of Assigned VESDA Detector<br />
&#8211; High Intensity Alarm LEDs<br />
&#8211; Remote Relay Option<br />
&#8211; 20-Segment Vertical Bar Graph Display<br />
&#8211; Alarm Threshold Indicators<br />
&#8211; Built-In Sounder for Audible Warning<br />
&#8211; Comprehensive Fault Reporting<br />
&#8211; Multi-mode Numeric Display (defaults to smoke obscuration)<br />
&#8211; Recessed Mounting Option</p>
<p>Specifications<br />
Operating Voltage (When used in detector unit, remote unit, or 19&#8243; rack): 18 to 30Vdc<br />
Operating Temp: 0 to 39° C<br />
Relative Humidity: 10 to 95% (non-cond.)</p>
<p>Module Only<br />
Dimensions (HWD): 130x105x30mm<br />
Operating Current: 60mA<br />
Alarm Current: 80mA @24Vdc</p>
<p>Mounted in Remote Box &#8211;<br />
Dimensions (WHD): 140 mm x 150 mm x 85 mm (5.5 in x 5.9 in x 3.4 in)<br />
Operating Current: 90mA<br />
Alarm Current: 110mA @24Vdc</p>
<p>The VRT-T00 is a VESDA LaserINDUSTRIAL display with a remote termination card. No Relays.</p>
]]></content:encoded>
										</item>
		<item>
		<title>LaserPLUS Handheld Programmer c/w Cable</title>
		<link>http://fireandsafetywa.com.au/product/laserplus-handheld-programmer-c-w-cable/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/laserplus-handheld-programmer-c-w-cable/</guid>
				<description><![CDATA[The LaserPLUS Handheld Programmer including a lead for temporary connection of a programmer to a network via a VESDAnet socket.]]></description>
								<content:encoded><![CDATA[<p>The LaserPLUS Handheld Programmer Module allows direct access to all VESDAnet devices on a VESDA smoke detection system.  It allows configuration and status reporting of detectos, displays and interfaces and is required when installing, commissioning and maintaining a VESDA network.  By incorporating a user friendly menu, navigation through the comprehensive features of VESDAnet is convenient and simple.</p>
<p>The VESDA LCD hand held Programmer including a lead for temporary connection of a programmer to a network via a VESDAnet socket.</p>
<p>Specifications<br />
Dimensions: 105x135x60mm<br />
Screen Display Size: 70x37mm<br />
Supply Voltage: 18 &#8211; 30Vdc<br />
Power (W) @24VDC: 1.68<br />
Current (mA) @24VDC: 70mA</p>
]]></content:encoded>
										</item>
		<item>
		<title>VESDAnet PC Link High Level Interface, Sliding Window</title>
		<link>http://fireandsafetywa.com.au/product/vesdanet-pc-link-high-level-interface-sliding-window/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/vesdanet-pc-link-high-level-interface-sliding-window/</guid>
				<description><![CDATA[The VESDA Sliding Windows High Level Interface (HLI) links your VESDAnet* with PC software monitoring and configuring tools such as Xtralis VSM4 and Xtralis VSC.]]></description>
								<content:encoded><![CDATA[<p>The VESDA Sliding Windows High Level Interface (HLI) links your VESDAnet* with PC software monitoring and configuring tools such as Xtralis VSM4 and Xtralis VSC.  To configure and monitor devices on VESDAnet, your HLI must be connected to a VESDAnet socket card.<br />
Direct Access to the Network<br />
By interfacing with PC monitoring and configuring tools, the Sliding Windows HLI allows you to easily configure, manage and monitor your entire VESDA network.</p>
<p>Simple Configuration and Seamless Data Transfer<br />
Your HLI is easily configured using your Xtralis VSC or Xtralis VSM4 software packages.  The Sliding Windows model provides seamless data transfer from your VESDAnet to your PC.</p>
<p>Designed for Small or Large Networks<br />
VESDA Sliding Windows HLIs are designed to suit your individual system design.  The VHX-0210 is ideally suited for small networks of up to 40 devices, while the VHX-0200 is designed for large networks of up to 200 devices.</p>
<p>Modem Support<br />
The VHX-0210 has modem (dial-in or dial out) capabilities allowing you full remote notification and interrogation functionality on networks of up to 40 devices.</p>
<p>Features<br />
&#8211;  Direct access and monitoring of your entire VESDAnet system<br />
&#8211; Designed for small or large networks<br />
&#8211; VHX-0210 includes modem support for remote notification &#038; interrogation<br />
&#8211; Seamless data transfer from your VESDAnet to your PC<br />
&#8211; Easily configured using Xtralis configuring and monitoring software packages</p>
<p>Specifications<br />
Power Consumption: 1.68W (Stable state i.e. no alarms and no fault conditions)<br />
Supply Voltage: 24Vdc<br />
Current Consumption: 70mA<br />
Dimensions: 192x110x40mm<br />
Weight: 0.4kg (0.9lbs)<br />
RS-232 9-way serial cable (male-female) for connection to PC (Identical to VSP-509)</p>
]]></content:encoded>
										</item>
		<item>
		<title>VESDAnet Simplex High Level Interface, Sliding Window</title>
		<link>http://fireandsafetywa.com.au/product/vesdanet-simplex-high-level-interface-sliding-window/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/vesdanet-simplex-high-level-interface-sliding-window/</guid>
				<description><![CDATA[The VESDA ModBus High Level Interface (HLI) links your VESDAnet1 with PC software monitoring tools, Building Management Systems (BMSs) or Fire Alarm Control Panels (FACPs), otherwise known as`host’, that support the ModBus protocol.]]></description>
								<content:encoded><![CDATA[<p>The VESDA ModBus High Level Interface (HLI) links your VESDAnet1  with PC software monitoring tools, Building Management Systems (BMSs) or Fire Alarm Control Panels (FACPs), otherwise known as`host’, that support the ModBus protocol. ModBus HLI Type 1 (VHX-0400) which echoes each character received on the RS232 link back to the host together with reply message.  One ModBus HLI is used to interface to a VESDAnet. Modbus HLI supports up to a maximum of 40 VESDA detectors on a VESDAnet.  The Modbus HLI supports VESDAnet detector zone numbers between 1 to 200. The Modbus HLI divides up the address range into to 7 logical networks. For example the first 30 addresses are considered in network 1, addresses between 31 to 60 are in network 2 and so on.</p>
<p>Smoke and Alarm Levels<br />
The Smoke Level is reported relative to the Fire Alarm threshold where the full scale is 20.  For example, if the Fire Alarm threshold is 0.5 %obs/m, a level of 0.1%obs/m is<br />
reported as 4. In other words, the Actual Smoke level = (Reported smoke value * Fire1 Threshold) / 20.</p>
<p>Faults<br />
All VESDAnet faults are mapped on one or more of the Modbus HLI faults which arelisted below:<br />
&#8211; Head Fault<br />
&#8211; Head Fault (Battery and Mains)<br />
&#8211; Head Fault (Scanner2, and<br />
&#8211; Flow Fault<br />
VESDAnet faults categorised as network faults are mapped onto all zones, whereas zone faults are mapped onto that particular zone.</p>
<p>Features<br />
&#8211; Direct access and monitoring of your VESDAnet system.<br />
&#8211; Seamless data transfer.<br />
&#8211; Easily configured using Xtralis configuring</p>
<p>Specifications<br />
Power Consumption: 1.68W (Quiescent)<br />
Supply Voltage: 24VDC<br />
Current Consumption: 70mA<br />
Weight: 0.4kg (0.9lbs)<br />
Dimensions: 188x98x40mm</p>
]]></content:encoded>
										</item>
		<item>
		<title>VESDAnet PC Link High Level Interface, Open Protocol</title>
		<link>http://fireandsafetywa.com.au/product/vesdanet-pc-link-high-level-interface-open-protocol/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/vesdanet-pc-link-high-level-interface-open-protocol/</guid>
				<description><![CDATA[The VESDA Open Protocol High Level Interface (HLI) links you VESDAnet with PC software monitoring tools, Building Management Systems (BMSs) and Fire Alarm Control Panels (FACPs), otherwise known as 'host'.]]></description>
								<content:encoded><![CDATA[<p>The VESDA Open Protocol High Level Interface (HLI) links your VESDAnet1 with PC software monitoring tools, Building Management Systems (BMSs) and Fire Alarm Control Panels (FACPs), otherwise known as ‘host’. The VESDAnet PC LInk HIgh Level Interface, Open Trotocol runs on a master-slave communication.  In the master-slave model, the host supervises the communications link between itself and the HLI (slave) by regularly polling the HLI to determine whether there has been a change in the status of a detector on VESDAnet. In response to polling by the host, the HLI generates a single response which is sent back to the host. In this way, no unsolicited messages are sent from the HLI to the host. Depending on the polling strategy adopted, the Master/Slave Open Protocol HLI is able to report any and all fire alarms within a few seconds of a detector going into alarm. Exact performance is dependent on the polling strategy adopted.</p>
<p>Features<br />
• Direct access and monitoring of your VESDAnet system.<br />
• Seamless data transfer.<br />
• Easily configured using Xtralis configuring and monitoring software packages.</p>
<p>Specifications<br />
Power Consumption: 1.68W (Quiescent)<br />
Supply Voltages: 24VDC<br />
Current Consumption: 70mA (Quiescent)<br />
Dimensions: 188mm x 98mm x 40mm<br />
Weight: 0.4kg (0.9lbs)<br />
Supplied with: VESDAlink RS-232 9-way cable (male-female)<br />
VESDAnet RS-485 15-way cable (male-female)</p>
]]></content:encoded>
										</item>
		<item>
		<title>VESDA Test Transformer</title>
		<link>http://fireandsafetywa.com.au/product/vesda-wire-burn-test-kit/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/vesda-wire-burn-test-kit/</guid>
				<description><![CDATA[Xtralis Test Transformer VTT-10000 (previously known as the Hot Wire Test – Power Supply Unit (PSU)) is a tool used to test very early warning aspirated smoke detection equipment.]]></description>
								<content:encoded><![CDATA[<p>VESDA Test Transformer VTT-10000 (previously known as the Hot Wire Test – Power Supply Unit (PSU)) is a tool used to test very early warning aspirated smoke detection equipment.</p>
<p>The unit generates a high current that passes through a test cable in order to heat it, which in turn causes its insulation to burn giving off smoke. The maximum operating time for the unit is three minutes and then it must be left immediately to cool it off for a period of at least seven minutes. On State: When the unit is turned on, the “POWER” indicator flashes a green light and the power is applied to the output terminals until the set time has elapsed. Off State: Once the timer has timed out, the output is switched off and the “OUT” indicator illuminates a red light while the “POWER” indicator remains illuminated.</p>
<p>Timer<br />
A timer is incorporated to provide a selectable burn period of up to 3 minutes.<br />
The timer also helps to prevent the unit being inadvertently left on for an extended period.<br />
The timer is reset when the switch is turned off and will run for the set period when the switch is turned on again.</p>
<p>Thermal Switch<br />
The unit is protected against over-temperatures by a thermal switch.<br />
Regardless of the power presence, this switch will not allow operation for an extended period (up to an hour) once turned on. Moreover, the thermal switch cannot be bypassed or reset manually.</p>
]]></content:encoded>
										</item>
		<item>
		<title>VSM4 Primary Site Licence</title>
		<link>http://fireandsafetywa.com.au/product/vsm4-primary-site-licence/</link>
				<pubDate>Sun, 07 Oct 2018 13:34:42 +0000</pubDate>
		<dc:creator><![CDATA[AJBPIKE]]></dc:creator>
		
		<guid isPermaLink="false">https://fireandsafetywa.com.au/product/vsm4-primary-site-licence/</guid>
				<description><![CDATA[Xtralis VSM4 provides full and comprehensive integration of your ASD system, including the VSM4 Central Site License - Primary PC]]></description>
								<content:encoded><![CDATA[<p>Xtralis VSM4 provides full and comprehensive integration of your VESDA and ICAM smoke and gas detection systems.<br />
Including, VSM4 Central Site License &#8211; Primary PC</p>